UST Program - LG 113

UST Program – LG 113

Issue Date: April 18, 1997
Updated: August 12, 2015

Franklin Fueling Systems
(Originally listed as INCON Intelligent Controls, Inc.)

Tank Sentinel TS-1000EFI , TS-1001/TS-2001, and TS-5xxx Series with TSP-HIS BriteSensor; Tank Sentinel TS-1000/TS-2000, TS-1001/TS-2001, and TS-5xxx Series with TSP-HLS Standard Sensor, TSP-ULS Standard Sensor and TSP-UHS Standard Sensor

INTERSTITIAL DETECTOR (LIQUID-PHASE)

 

Detector:

Output type: qualitative
Sampling frequency: continuous
Operating principle: magnetic switch

Test Results:

50% by weight
ethylene glycol in water
30% by weight
calcium chloride in water
TSP-HIS BriteSensor
 
high*
low*
high
low
Response time (min:sec)
17:41
16:47
17:28
16:56
Recovery time (min)
<1
<1
<1
<1
Product activation height (cm)
19.56
2.53
19.40
2.50
unleaded
gasoline
synthetic gasoline
   
diesel***
heating
oil #2
 
water
E 85 waste oil
TSP-HLS Standard Sensor
   
Detection time (min:sec)
10:09
10:14
09:55
10:25
09:25
--
--
Fall time (min)
<1
<1
<1
<1
<1
--
--
Product activation height (cm)
5.64
N/D**
N/D
N/D
N/D
--
--
Lower detection limit (cm)
5.03
5.03
4.93
5.17
4.77
--
--
TSP-ULS Standard Sensor              
Detection time (min:sec)
03:50
03:49
03:50
03:41
03:34
<1
<1
Fall time (min)
<1
<1
<1
<1
<1
<1
<1
Product activation height (cm)
2.70
N/D
N/D
N/D
N/D
2.59
--
Lower detection limit (cm)
1.93
1.97
1.93
1.80
1.80
2.58
1.17
TSP-UHS Standard Sensor  
 
 
 
 
   
Detection time (min:sec)
03:50
03:49
03:50
03:41
03:34
<1
<1
Fall time (min)
<1
<1
<1
<1
<1
<1
<1
Product activation height (cm)
2.70
N/D
N/D
N/D
N/D
2.96
--
Lower detection limit (cm)
1.93
1.97
1.93
1.80
1.80
2.95
1.22

*The "high" and "low" refer to high and low level alarm points of hydrostatic sensors.

** See glossary.

***This evaluation determined the sensor's responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

Comments:

TSP-HIS BriteSensor is intended to monitor level of either ethylene glycol or calcium chloride solutions in interstitial or annular space of a double-walled tank. Activates if any significant gain or loss of solution occurs.

Comparison of Tank Sentinel TS-1001/TS-2001 and TS-5xxx series consoles with Tank Sentinel TS-1000(including EFI)//TS-2000 series consoles showed comparable results when evaluated with representative sensors.

TSP-UHS is the same as the TSP-ULS sensor except that the float has been inverted so that it may be used to monitor the brine reservoir of containment sumps. An alarm condition will occur when the fluid level drops below the end of the sensor.

Sensors are reusable.

Franklin Fueling Systems Evaluator: Carnegie Mellon Research Institute
3760 Marsh Road Tel:(412) 268-3495
Madison, WI 53718 Dates of Evaluation:03/20/95, 01/30/96
Tel: (800) 225-9787 Evaluator: Ken Wilcox Associates
email: info@franklinfueling.com Tel: (816) 443-2494
URL: www.franklinfueling.com Date of Evaluation: 4/1/08, 11/20/10, 10/18/11

 

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded "Disclaimer" page.

 

 
 

.