PermAlert
LiquidWatch Leak Detection System LW64-IS with PHLR-LW and PHLR-P-LW Hydrocarbon Probes

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type qualitative
Sampling frequency continuous
Operating principle product soluble

Test Results:

PHLR-S/L and PHLR-P-S/L Hydrocarbon Probes unleaded gasoline
Response time (sec) 24
Recovery time (hour) >16
Product activation height (mm) 2.0
Lower detection limit (mm) 3.9

Specificity Results (in addition to above):
Activated:  diesel, jet fuel.
Not activated: water.

Comments:
Sensors are reusable.
“PHLR-S/L” sensors are designed for operation in ambient pressure environments while
“PHLR-P-S/L” sensors are designed for operation in pressurized environments.

PermAlert
7720 N. Lehigh Ave.
Niles, IL 60714-3491
Tel:  (847) 966-2235
Evaluator: Trace Laboratories
Tel: (847) 934-5300
Date of Evaluation: 02/23/07  