Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
UST Program - LG 113

UST Programs - LG 113

Issue Date: May 2, 2000 

 

Tanknology - NDE

TLD-1 (for Flexible Pipelines)

LINE TIGHTNESS TEST METHOD

Certification Leak rate of 0.1 gph with PD = 99.9% and PFA = 0.1%.
Leak Threshold 0.05 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel.
Specification System tests flexible pipelines. 
Tests are conducted at 150% operating pressure. 
Mechanical line leak detector must be removed or isolated from pipeline for duration of test.
Pipeline Capacity Maximum of 50 gallons.
Waiting Time Average of 1 hour.
Test Period 1 to 6 hours. Average is 2 hours 15 minutes. 
Test may not be ended until pass/fail criteria set by manufacturer has been met. 
Pipe deflection, vapor pockets, and large temperature differences may produce inconsistent readings. 
Testing must continue until stable conditions are present. 
Test data are acquired and recorded manually.
Comments Enviroflex pipeline wih a bulk modulus* of 1,280 was used during evaluation. 
*See glossary.

 

Tanknology - NDE

Evaluator:  Ken Wilcox Associates

8900 Shoal Creek Blvd. , Building 200

Tel:  (816) 443-2494

Austin , TX 78757

Date of Evaluation:  04/30/94

Tel:  (800) 800-4633

 