Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
UST Program - LG 113

UST Programs - LG 113

Issue Date: November 22, 1995
Revision Date: March 28, 2002
 

Veeder-Root

350 Series, Red Jacket ProMax UST Monitoring Systems Models ILS-350, TLS-350, 350R, 350PC, 350RPC
with Groundwater Sensors 794380-621, 622, 624

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

Detector:         

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

electrical conductivity

 

Test Results:

 

 

unleaded gasoline

synthetic gasoline

Detection time (min:sec)

8:55

6:18

Fall time (min:sec)

54:50

26:02

Lower detection limit (cm)

0.02

0.02

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s).

Calibration:
Sensor must be checked annually for operability or in accordance with manufacturer's instructions and, if necessary, calibrated or replaced.

Comments:
Sensors are reusable.

 

Veeder-Root

Evaluator:  Carnegie Mellon Research Institute

125 Powder Forest Dr.

Tel:  (412) 268-3495

Simsbury, CT  06070-2003

Dates of Evaluation:  11/20/91, 07/28/92

Tel:  (860) 651-2700

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.