- LG 113 Home Page
- Distribution Letter
- Disclaimer
- Equipment Type:
- Test Method Index
- LG 113 News
- Previous LG 113 - 16
- Leak Detection Equipment Review List
- Acceptable Test Protocols
- Glossary of Terms
- Monitoring System Certification
- Work Group
- Policy Memoranda:
- Maintenance Checklists:
UST Programs - LG 113
|
Issue Date: August 30, 2007 Western Fiberglass, Inc. Co-Flow
Hydraulic Interstitial Monitoring System CONTINUOUS INTERSTITIAL LINE MONITORING METHOD (LIQUID FILLED) Certification: Operating Principle: Alarm Conditions:
Previously conducted theoretical calculations and laboratory measurements confirm that dilution of the propylene glycol used in the interstice of the WFG system will produce a significant reduction in the alarm time. The use of diluted propylene glycol (from100% to 50%) will reduce the alarm time by a factor of approximately 7.2. For example, an alarm time of 80 minutes would be reduced to around 11 minutes. Calibration: Comments:
|
||||||||||||||||||||||||||||||||||||||||||
|
|
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Appearance
on this list is not to be construed as an endorsement by any regulatory
agency nor is it any guarantee of the performance of the method or equipment. |