- LG 113 Home Page
- Distribution Letter
- Disclaimer
- Equipment Type:
- New! Recent Equipment Type Additions/Revisions
- VPH Methods
- Test Method Index
- Acceptable E85 Leak Detection
- Acceptable Biodiesel Leak Detection
- Leak Detection Equipment Review List
- Acceptable Test Protocols
- Glossary of Terms
- Monitoring System Certification
- Work Group
- Policy Memoranda:
- Policy Memo #1
- Policy Memo #2
- Policy Memo #3
- Maintenance Checklists:
UST Program - LG 113
Issue Date: January 27, 2010
Beaudreau
Electric Marketing, LLC
Model MPC100 Controller with Models DCS140L, DCS140NL Liquid Sensors and Model DCS140D Discriminating Liquid Sensor
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
Output type: | qualitative (DCS140L & DCS140NL), discriminating (DCS140D) |
Sampling frequency: | continuous |
Operating principle: | float switch |
Test Results:
Model DCS140L LiquidSensor |
unleaded |
#2 diesel |
water |
E85 |
Detection time (sec) |
<1 |
<1 |
<1 |
<1 |
Fall time |
manual reset |
manual reset |
manual reset |
manual reset |
Precision - standard deviation (in) |
0.019 |
0.028 |
0.017 |
0.021 |
Lower detection limit (cm) |
1.064 |
1.094 |
0.915 |
1.086 |
Model DCS140NL Liquid Sensor |
|
|
|
|
Detection time (sec) |
<1 |
<1 |
<1 |
<1 |
Fall Time (sec) |
<1 |
<1 |
<1 |
<1 |
Precision - standard deviation (in) |
0.022 |
0.014 |
0.015 |
0.014 |
Lower detection limit (cm) |
1.211 |
1.068 |
0.918 |
1.077 |
Model DCS140D |
|
|
|
|
Detection time (sec) |
<1 |
<1 |
<1 |
- |
Fall time (sec) |
<1 |
<1 |
<1 |
- |
Precision - standard deviation (in) |
0.003 |
0.006 |
0.004 |
- |
Lower detection limit (cm) |
0.878 |
0.813 |
0.691 |
- |
Specificity Results:
Manufacturer and evaluator claim sensors will respond to any liquid but evaluator only tested for liquids identified above.
Manufacturer’s Specifications:
Manufacturer states that systems require no calibration.
Annual functional test required.
Model DCS140D generates alarms on fuel detection and high liquid while Models DCS140L and DCS140NL generate an alarm on liquid detection.
Comments:
Each sensor is reusable.
If liquid is detected at any of the threshold levels, a fuel alarm will be triggered.
The output from the system can be used to shut down the turbines when fuel is present or when water reaches the high level switch.
Beaudreau Electric Marketing, LLC |
Evaluator: Ken Wilcox Associates |
100 Mechanic Street |
Tel: (816) 443-2494 |
Pawcatuck, CT 06379 |
Date of Evaluation: 07/09/09 |
Tel: (860) 495-0522 |
|
|
|
|
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |
Appearance
on this list is not to be construed as an endorsement by any regulatory
agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable
laws and regulations.
For full details, please refer to our expanded "DISCLAIMER"