UST Programs - LG 113
Issue
Date: August 10, 2001
Pneumercator Company, Inc. TMS 2000, TMS 3000 with ES820-100 Non-Discriminating Liquid Sensor, ES820-200 Discriminating Liquid Sensor INTERSTITIAL DETECTOR (LIQUID-PHASE) Detector:
Test Results: *California requires annual certification of all leak detection equipment. The certification of discriminating sensors should include functional testing of both water and product detection capabilities. Model ES820-200: This sensor can only respond to liquid directly in contact with the detection element, and is unable to detect a product release floating on an existing pool of water whose height exceeds the level of the detection element.
Specificity Results:
|
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Appearance
on this list is not to be construed as an endorsement by any regulatory
agency nor is it any guarantee of the performance of the method or equipment. |