Continuous In-Tank Leak Detection Method
(Continuous Automatic Tank Gauging)

Click on the vendors specific Equipment Name to go to that Listing.

VENDOR
EQUIPMENT NAME
LEAK RATE/THRESHOLD / MAX TANK CAPACITY
Caldwell Systems Corp. Tank Manager Monitoring Systems with CITLDS(Ultrasonic Probe) 0.2 gph/N/A for qualitative methods/ 18,000 gallons
Dresser Wayne Europe TIG 5000 ATG System(Q0400-4xx Magnetostrictive Probe) 0.2 gph/0.1 gph/35,000 gallons
EBW, Inc. AutoStik II, AutoStik Jr. with SCALD 2.0(INCON TSP-LL2 Magnetostrictive Probe) Certification for those sold on or after March 1, 2004 0.2 gph/0.1 gph/49,336 gallons
Franklin Fueling Systems TS 750, 1000, 1001, 2000, 2001 with SCALD 2.0, TS-5, TS-608, TS-550, TS-5000(INCON TSP-LL2 Magnetostrictive Probe) 0.2 gph/0.1 gph/49,336 gallons
Hectronic GmbH Hectronic Optilevel Dynamic Leak Detection System,
Optilevel CITLDS (Capacitance Probe)
0.2 gph/0.1 gph/11,869 gallons (single tanks), 23,778 gallons (manifolded tanks)
INCON Intelligent Controls, Inc. TS 750, 1000, 1001, 2000, 2001 with SCALD 2.0, TS-5, TS-608, TS-550, TS-5000(INCON TSP-LL2 Magnetostrictive Probe) 0.2 gph/0.1 gph/49,336 gallons
OMNTEC Mfg., Inc. OEL 8000 II, K-OEL 8000 II Monitoring System with CITLDS (MTG-XX Magnetostrictive Probe) 0.2 gph/0.1 gph/18,000 gallons
OPW Fuel Management Systems (originally listed as Emco Electronics, Tuthill Transfer Systems) EECO System 1000,1000EG, 1500, 2000, 3000 and Galaxy ATG Systems (Q0400-4xx Magnetostrictive Probe) 0.2 gph/0.1 gph/35,000 gallons
Veeder-Root Marconi (originally listed as Gilbarco Environmental Products and later as Marconi Commerce Systems) EMC, EMC Basic, EMC Enhanced with CSLD, PAO265XXXX100, PA0300XXXX100 (Magnetostrictive Probe) 0.2 gph/0.16 gph(single tanks), 0.15(manifolded tanks)/38,170 gallons
Veeder-Root TLS-300i, 300J, 350, 350R, 350Plus, 450, Red Jacket ProMax Monitoring Systems with CSLD (Models 8463, 8473, 8493 Magnetostrictive Probes) 0.2 gph/0.16 gph/38,170 gallons