Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
UST Program - LG 113 - Line Tightness Test Methods

UST Program - LG 113 - Line Tightness Test Methods


Revision Date: May 23, 2007

Line Tightness Test Methods

Click on the vendors specific Equipment Name to go to that Listing.

VENDOR EQUIPMENT NAME LEAK RATE/THRESHOLD / MAX PIPELINE CAPACITY
Estabrook EZY CHEK Systems (originally listed as Horner EZY CHEK) EZY-Chek Manual Line Leak Detector 0.1 gph/0.05 gph/129 gallons
EZY-Chek Manual Line Leak Detector (for Flexible Pipelines) 0.1 gph/0.05 gph/101 gallons
EZY-Chek II Automatic Line Leak Detector 0.1 gph/0.05 gph/129 gallons
ProTank, Inc. LTH-5000 Line Tester 0.1 gph/0.05 gph/40 gallons
LTP-5000 Line Tester 0.1 gph/0.05 gph/41 gallons
Purpora Engineering, LLC (originally listed as Heath Consultants, Inc.) Petro Tite Line Tester 0.1 gph/0.05 gph/129 gallons
Purpora Engineering, LLC (originally listed as Heath Consultants, Inc.) Petro Tite Line Tester (for Flexible Pipelines) 0.1 gph/0.05 gph/49.6 gallons
Tanknology - NDE Proline Test Series III, Version 1.0 Line Test 0.1 gph/0.05 gph/41 gallons
PTK-88 0.1 gph/0.05 gph/40 gallons
TLD-1 Line Test 0.1 gph/0.05 gph/50 gallons
TLD-1 Line Test (Flexible Pipelines) 0.1 gph/0.05 gph/50 gallons
Praxair Services, Inc.
(originally listed as Tracer Research, Corp.)
Tracer Tight Line Test 0.1 gph and 0.005gph/A pipeline system should not be declared tight when tracer chemical is detected outside of the pipeline/Not limited by capacity
Training and Services Corp. (originally listed as Hasstech) AcuRite (for Rigid and Flexible Pipelines) 0.1 gph/0.01 gph/150 gallons
Triangle Environmental, Inc. TEI Model LT-3, Version 1.0 0.1 gph/0.05 gph/80 gallons
Western Environmental Resources Model PLT-100R 0.1 gph/0.05 gph/80 gallons