Issue Date: September 1,
2006
Revision Date: February 21, 2008
Franklin
Fueling Systems
TS-LS500, TS-LS500E
Series
(For Rigid and/or Flexible Piping)
AUTOMATIC
ELECTRONIC LINE LEAK DETECTOR
|
Certification
|
Leak
rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100%
and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure*
with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this
leak rate and pressure were certified using an equivalent
leak rate and pressure, in accordance with an acceptable
protocol. |
|
Leak
Threshold
|
1.5
gph for leak rate of 3.0 gph.
0.1 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold. |
|
Applicability
|
Gasoline,
diesel, aviation fuels, fuel oil #4, waste oil, kerosene.
Other liquids may be tested after consultation with the
manufacturer. |
|
Specification
|
On
pressurized rigid flexible, or combination rigid and flexible
pipelines, system can perform
3.0 gph, 0.2 gph,and 0.1 gph tests.
Tests are conducted at operating pressure. |
|
Pipeline
Capacity
|
Maximum
of 312.2 gallons for steel and fiberglass pipelines (examples:
480 feet of 4 inch line; 671 feet of 3 3/8 inch line ).
Maximum of 95.4 gallons for flexible pipelines (examples:
260 feet of 3 inch line; 1040 feet of 1 ½ inch
line).
Maximum of 415.8 gallons for combination rigid and flexible
pipelines (the capacity of the flexible component cannot
exceed 95.4 gallons). |
|
Waiting
Time
|
None
between delivery and testing.
None between dispensing and testing for leak rate of 3.0
gph.
Depending on temperature stability, 1½ to 10 hours
between dispensing and testing for leak rates of 0.2 gph
and 0.1 gph. |
|
Test
Period
|
Response
time is 1 to 2 minutes for leak rate of 3.0 gph.
Minimum of 25 minutes for leak rate of 0.2 gph.
Minimum of 34 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor. |
|
System
Features
|
Permanent
installation on pipeline.
Automatic testing of pipeline every 45 minutes for leak
rate of 3.0 gph.
Automatic testing of pipeline when pump has been idle
for 2 hours for leak rate of 0.2 gph.
Automatic testing of pipeline when pump has been idle
for 3½ hours for leak rate of 0.1 gph.
Pump shutdown, indicator light and alarm activation if
leak is declared for 3.0 gph and 0.2 gph tests. |
|
Calibration
|
System
must be checked annually and, if necessary, calibrated
in accordance with manufacturer's instructions.
Equipment
must be checked annually for capability of detecting
a line leak of 3.0 gph and, if necessary, calibrated
in accordance with manufacturer's instructions. |
|
Franklin
Fueling Systems
|
Evaluator: Ken Wilcox Associates
|
|
3760
Marsh Road
|
Tel: (816) 443-2494
|
|
Madison,
WI 53718
|
Date
of Evaluation: 06/23/95,
09/10/98, 02/28/06
|
|
Tel:
(800) 225-9787
|
08/28/06,
01/10/08
|
|
E-Mail:
info@franklinfueling.com |
|
|
URL:
www.franklinfueling.com |
|
|