Issue Date: November 22, 1995
Revision Date: June 20, 2008

Veeder-Root

350 Series, TLS-450 Series, Red Jacket ProMax UST Monitoring Systems Models ILS-350,
TLS-350, 350R, 350PC, 350RPC with Groundwater Sensors 794380-621, 622, 624

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

Detector:

Output type: qualitative
Sampling frequency: continuous
Operating principle: electrical conductivity

Test Results:

Detectiontime (min:sec) unleaded gasoline synthetic gasoline
8:55 6:18
Fall time (min:sec) 54:50 26:02
Lower detection limit (cm) 0.02 0.02

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s).

Calibration:
Sensor must be checked annually for operability or in accordance with manufacturer's instructions and, if necessary, calibrated or replaced.

Comments:
Sensors are reusable.
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.

Veeder-Root
125 Powder Forest Dr.
Simsbury, CT  06070-2003
Tel:  (860) 651-2700
E-mail:  dhalla@veeder.com
URL:  www.veeder.com/dynamic/index.cfm
Evaluator:  Carnegie Mellon Research Institute
Tel:  (412) 268-3495
Dates of Evaluation:  11/20/91, 07/28/92 Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluations: 3/3/2008


 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |


Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.