Issue
Date: January 11, 2001
Containment
Solutions, Inc.
(originally listed as
Fluid Containment and O/C Tanks)
FOVF
600B, FOVF 600S Non-Discriminating Sensors for High Level
Overfill (Brass, Steel); FCBS 700 Non-Discriminating Sensor
for Collars, Bulkheads, Sumps; FDAS 710 Non-Discriminating
Sensor for Dry Annular Spaces; FHRB 810 Non-Discriminating
Sensor for Reservoirs
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector:
|
Output type:
|
qualitative
|
|
Sampling frequency:
|
continuous
|
|
Operating
principle:
|
float
switch
|
Test
Results:
Non-Discriminating Sensors
|
unleaded
gasoline
|
diesel
|
water
|
|
FOVF
600B, FOVF 600S (Overfill)
|
|
|
|
|
Lower Detection Limit (in)
|
3.32
|
3.26
|
3.18
|
|
Precision-Standard Deviation
(in)
|
0.0051
|
0.0025
|
0.0037
|
|
Detection time (sec)
|
<1
|
<1
|
<1
|
|
Fall time (sec)
|
<1
|
<1
|
<1
|
|
FCBS
700 (Collars, Bulkheads,Sumps)
|
|
|
|
|
Lower Detection Limit (in)
|
0.99
|
0.97
|
0.87
|
|
Precision-Standard Deviation
(in)
|
0.0040
|
0.0027
|
0.0043
|
|
Detection time (sec)
|
<1
|
<1
|
<1
|
|
Fall time (sec)
|
<1
|
<1
|
<1
|
|
FDAS
710 (Dry Annular Spaces)
|
|
|
|
|
Lower Detection Limit (in)
|
0.44
|
0.43
|
0.42
|
|
Precision-Standard Deviation
(in)
|
0.0025
|
0.0041
|
0.0031
|
|
Detection time (sec)
|
<1
|
<1
|
<1
|
|
Fall time (sec)
|
<1
|
<1
|
<1
|
|
FHRB 810 (Reservoirs
- Low level float)
|
|
|
|
|
Lower Detection Limit (in)
|
2.57
|
2.53
|
2.31
|
|
Precision-Standard Deviation
(in)
|
0.0042
|
0.111
|
0.0042
|
|
Detection time (sec)
|
<1
|
<1
|
<1
|
|
Fall time (sec)
|
<1
|
<1
|
<1
|
|
FHRB
810 (Reservoirs - High level float)
|
|
|
|
|
Lower Detection Limit (in)
|
13.31
|
13.24
|
13.01
|
|
Precision-Standard Deviation
(in)
|
0.0080
|
0.0061
|
0.0042
|
|
Detection time (sec)
|
<1
|
<1
|
<1
|
|
Fall time (sec)
|
<1
|
<1
|
<1
|
Comments:
Control
panel models:
CPF 1, CPF 2, CPF 3, CPF 4 for liquid level sensors;
CPI 1D, CPI 1H, CPI 1N inventory control for liquid level sensors and 1 tank;
CPD 1, CPD 2, CPD 4 for discriminating liquid level sensors;
CPI 4 inventory control for liquid level sensors and up to
4 tanks;
BOMC battery operated control cap for liquid level sensors;
CCF 1DA battery operated control cap for dry annulus monitoring;
CCF
2 battery operated control cap for hydrostatic reservoir monitoring.
|
Containment Solutions, Inc.
|
Evaluator: Ken Wilcox Associates
|
|
5150 Jefferson Chemical
|
Tel: (816) 443-2494
|
|
Conroe, TX 77301-6834
|
Date
of Evaluation: 06/11/99
|
|
Tel: (800) 628-2657
|
|
|