SiteSentinel Controller with
Optical Sensor Part #30-3223

OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

metal oxide semiconductor (Part #30-3222), Optical (Part #30-3223) 

Test Results:

Unleaded gasoline

diesel

water

Part #30-3222

Detection time (sec)

5.946

30.948

-

Fall time (sec)

 *

**

-

Part #30-3223

 

 

 

Detection time (sec)

<1

<1

<1

Fall time (sec)

<1

<1

<1

Lower detection limit (in)

0.571

0.561

0.592

*Evaluator notes that because of the geometry of the vapor sensors and their varied installation options, the threshold level was not measured.
** Evaluator notes that this sensor resets very slowly and that controller should be adjusted or replaced after each alarm.

Specificity Results:
Part #30-3222 responds to hydrocarbons only.
Part #3223 works with any liquid.

Comments:
Performance of these sensors degrades after exposure to high concentrations of hydrocarbons.

 

OPW Fuel Management Systems

Evaluator:  Ken Wilcox Associates

6900 Santa Fe Dr.

Tel:  (816) 443-2494

Hodgkins, IL 60525-9909

Dates of Evaluation:  08/03/00

Tel:  (708) 485-4200

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.