UST Program - LG 113 - Aboveground Storage Tank Method
Above Ground Storage Tank Method
Click on the vendors specific Equipment Name to go to that Listing.
VENDOR |
EQUIPMENT NAME |
LEAK RATE / THRESHOLD / MAX TANK CAPACITY |
Leak Detection Technologies (originally listed as Leak Detection Technologies International) | MDleak Enhanced Leak Detection Method (Aboveground Storage Tank Leak Detection Method) | 0.005 gph, or greater/ A tank system should not be declared tight when tracer chemical greater than the background level is detected outside of the tank system. Not limited by capacity. |
Mass Technology Corp. | Precision Mass Measurement Systems SIM-1000 & CBU-1000 AST Leak Detection System | 1.717 gph and 0.859 gph/A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds this threshold./Surface area 30,172 sq. ft. and diameter 196 feet. |
Praxair Services, Inc. | Tracer Tight for Large Aboveground Storage Tanks | 0.1 gph and 0.005 gph A tank system should not be declared tight when tracer chemical greater than the background level is detected outside of the tank system. Not limited by capacity. |