Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113 - Bulk Underground Storage Tank Leak Detection Methods

UST Program - LG 113 - Bulk Underground Storage Tank Leak Detection Methods

Revision Date: June 2008

Bulk Underground Storage Tank Leak Detection Method
(50,000 gallons or greater)

Click on the vendors specific Equipment Name to go to that Listing.

VENDOR EQUIPMENT NAME LEAK RATE / THRESHOLD /
MAX PRODUCT SURFACE AREA
ASTTest Services, Inc. ASTTest Mass Balance Leak Detection System [(product surface area in ft² ÷ 5,575 ft²) x 0.88 gph]/ [(product surface area in ft² ÷ 5,575 ft²) x 0.44 gph]/13,938 ft²
Engineering Design Group EDG XLD 2000 Plus (Revision 1.02) Leak Detection System
(MTS DDA Magnetostrictive Probe)
[(product surface area in ft² ÷ 12,074 ft²) x 1.92 gph]/[(product surface area in ft² ÷ 12,074 ft²) x 0.96 gph]/12,076 ft².
Ronan X-76 CTM Automatic Tank Gauging System
(MTS Level Plus UST Probe)
[(product surface area in ft² ÷ 564 ft²) x 0.2 gph]/[(product surface area in ft² ÷ 564 ft²) x 0.96 gph]/846 ft².
Leak Detection Technologies, Inc. MDleak Enhanced Leak Detection Method (Bulk 50,000 gallons or greater) 0.005 gph / when the chemical marker detected exceeds the background level outside of the pipeline / Not limited by capacity
Mass Technology Corp. Precision Mass Measurement System, SIM-1000 and CBU-1000 (24 hour test) [(product surface area in ft² ÷ 1,257 ft²) x 0.1 gph]/[(product surface area in ft² ÷ 1,257 ft²) x 0.05 gph]/3,143 ft².
Precision Mass Measurement System, SIM-1000 and CBU-1000 (48 hour test) [(product surface area in ft² ÷ 6,082 ft²) x 0.294 gph]/[(product surface area in ft² ÷ 6,082 ft²) x 0.147 gph]/6,082 ft².
Precision Mass Measurement System, SIM-1000 and CBU-1000 (72 hour test) [(product surface area in ft² ÷ 14,200 ft²) x 0.638 gph]/[(product surface area in ft² ÷ 14,200 ft²) x 0.319 gph]/35,500 ft².
Praxair Services, Inc.
(originally listed as Tracer Research, Corp.)
Tracer ALD 2000 Automated Tank Tightness Test 0.1 gph/ A tank system should not be declared tight when tracer chemical or hydrocarbon greater that the background level is detected outside of the tank./Not limited by capacity.
Universal Sensors and Devices, Inc. LTC-1000
(Mass Buoyancy Probe)
[(product surface area in ft² ÷ 14,244 ft²) x 1.4 gph]/[(product surface area in ft² ÷ 14,244 ft²) x 0.7 gph]/35,610 ft².
LTC-2000
(Differential Pressure Probe)
[(product surface area in ft² ÷ 14,244 ft²) x 3.0 gph]/[(product surface area in ft² ÷ 14,244 ft²) x 1.5 gph]/35,610 ft².
Varec, Inc. (originally listed as Coggins Systems, Inc. and later as Endress+Hauser Systems and Gauging) Fuels Manager and Remote Terminal Unit (RTU/8130)
(MTS Magnetostrictive Probe)
[(product surface area in ft² ÷ 616 ft²) x 0.2 gph]/[(product surface area in ft² ÷ 616 ft²) x 0.1 gph]/924 ft²
Fuels Manager with Barton Series 3500 ATG
(48 hour test)
(72 hour test)
[(product surface area in ft² ÷ 6,082 ft²) x 2.0 gph]/[(product surface area in ft² ÷ 6,082 ft²) x 1.0 gph]/15,205 ft².

FuelsManager with Enraf 854 ATG (Servo Buoyancy Probe) [(product surface area in ft² ÷ 11,786 ft²) x 3.00 gph]/[(product surface area in ft² ÷ 11,786 ft²) x 1.50 gph]/ 11,786 ft²
FuelsManager with MTS M-Series ATG (MTS Magnetostrictive Probe) [(product surface area in ft² ÷ 11,786 ft²) x 4.50 gph]/[(product surface area in ft² ÷ 11,786 ft²) x 2.25 gph]/ 11,786 ft²
Vista Research, Inc. and Naval Facilities Engineering Service Center LRDP-24 (V1.0.2, V1.0.3) [(product surface area in ft² ÷ 6,082 ft²) x 2.0 or 3.0 gph]/[(product surface area in ft² ÷ 6,082 ft²) x (2.0 or 3.0 gph - 0.223 gph)]/15,205 ft².
LRDP-48 (V1.0.2, V1.0.3) [(product surface area in ft² ÷ 6,082 ft²) x 2.0 or 3.0 gph]/[(product surface area in ft² ÷ 6,082 ft²) x (2.0 or 3.0 gph - 0.188 gph)]/15,205 ft².
LRDP-24 (V1.1) [(product surface area in ft² ÷ 6,082 ft²) x 0.856 gph]/[(product surface area in ft² ÷ 6,082 ft²) x 0.632 gph]/15,205 ft².
LRDP-48 (V1.1)

[(product surface area in ft² ÷ 6,082 ft²) x 0.749 gph]/[(product surface area in ft² ÷ 6,082 ft²) x 0.563 gph]/15,205 ft².

 
 

.