LG 113 RESOURCES
- LG 113 Home Page
- Distribution Letter
- Disclaimer
- Equipment Type:
- New! Recent Equipment Type Additions/Revisions
- VPH Methods
- Test Method Index
- Acceptable E85 Leak Detection
- Acceptable Biodiesel Leak Detection
- Leak Detection Equipment Review List
- Acceptable Test Protocols
- Glossary of Terms
- Monitoring System Certification
- Work Group
- Policy Memoranda:
- Policy Memo #1
- Policy Memo #2
- Policy Memo #3
- Maintenance Checklists:
UST Program - LG 113 - Continuous Interstitial Monitoring Method (Liquid Filled)
Revision Date: October 19, 2007
Continuous
Interstitial Monitoring Method
(Liquid Filled)
Click on the vendors specific Equipment Name to go to that Listing.
VENDOR |
EQUIPMENT NAME |
LEAK RATE/THRESHOLD
/MAX TANK OR MAX PIPELINE LENGTH* |
Ameron International | Dualoy 3000/LCX and MCX Pipe Monitoring System Brine Filled Interstitial Space | Brine solutions is used to fill the Ameron Dualoy 3000/LCX and MCX fiberglass double-wall pipe interstice. A reservoir at the high point of the system contains a dual-point level sensor that will alarm if the liquid level is too high or too low./344 feet |
Dualoy 3000/LCX and MCX Pipe Monitoring System Brine Filled Pressurized Interstitial Space | Brine solution is used to fill the Ameron Dualoy 3000/LCX and MCX fiberglass double-wall pipe interstice, which is pressurized using an air compressor or gas bottle. A reservoir contains a dual-point level sensor that will alarm if the liquid level is too high or too low./344 feet | |
Containment Solutions, Inc. (originally listed as Fluid Containment and O/C Tanks) | FCI
Liquid Filled Interstitial Monitor Tank Model DWT6 with Model FHRB 810 Level Sensor |
A Fluid reservoir is attached to the top of the tank and is open to the interstice through the bottom and is normally filled with a brine solution in freeze areas or water in non-freeze areas. The reservoir is equipped with a dual-point level sensor to provide for low level and high level alarms./For use with all Containment Solution tank sizes. |
Western Fiberglass, Inc. | Co-Flow Hydraulic Interstitial Monitoring System | Propylene glycol is used to fill the Western Fiberglass, Inc., double-walled/coaxial flexible pipeline interstice. Two reservoirs are used to contain the liquid, one at each end of the system./200feet |
Co-Flow
Hydraulic Interstitial Monitoring System Propylene Glycol Filled Pressurized Interstitial Space |
Propylene glycol is used to fill the Western Fiberglass, Inc., double-walled/coaxial flexible pipe interstice. A pressurized cylinder is used to maintain pressure in the reservoir./200 feet | |
Liquid-Filled
Reservoir for Double-Wall Sumps with Liquid Sensor
Models WF-3 and WF-750 |
Propylene glycol is used to fill the Western Fiberglass double-walled sump or under dispenser containment sump interstice./Not applicable. | |
Xerxes Corp. | Xerxes Trucheck Continuous Leak Detection System | A Fluid reservoir is attached to the top of the tank and is open to the interstice through the bottom and is filled with a brine solution. The reservoir is equipped with an electronic probe to provide for low level and high level alarms./For use with all Xerxes tank sizes. |