Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Program - LG 113

Issue Date: April 18, 1997
Revision Date: October 27, 2005

Sequence Contols, Inc.
(originally listed as Armstrong Monitoring, Corp.)

AMC 5100
Leak Detection Cable AMC-5007

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

Detector:

 Output type:

qualitative

 Sampling frequency:

continuous

 Operating principle:

electrical conductivity

Test Results:*

 

unleaded gasoline

Detection time (sec):

35

Fall time (min:sec):

02:30

Lower detection limit (cm):

0.04

*For tests conducted with 0.32 cm of floating product.

Manufacturer's specifications:
Operating temperature: 32 degrees F to 104 degrees F (0 degrees C to 40 degrees C).

Comments:
Sensors are reusable.

 

Sequence Controls, Inc.

Evaluator:  Environment Canada

150 Rosamond Street

Tel:  (613) 991-1108

Carleton Place, Ontario, Canada K7C 1V2

Date of Evaluation:  12/03/92

Tel:  (613) 257-7356  
E-mail: kvanspengen@sequencecontrols.com  

URL: www.sequencecontrols.com

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.