FE Petro, Inc.

STP-MLD-D Pipeline Leak Detector

AUTOMATIC MECHANICAL LINE LEAK DETECTOR

Certification Leak rate of 3.0 gph with PD = 100% and PFA = 0%.
Leak Threshold 2.0 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Diesel
Specification System tests steel and fiberglass pipelines. 
Tests are conducted at operating pressure.
Pipeline Capacity Maximum for rigid system is 341 gallons.
Waiting Time None between delivery and testing. 
None between dispensing and testing.
Test Period Average response time is 1 minute.
System Features Permanent installation on pipeline. 
Automatic testing of pipeline. Preset threshold. 
Single test to determine if pipeline is leaking. 
Restricted flow to dispenser if leak is declared.
Calibration Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions.

 

FE Petro, Inc.

Evaluator:  Ken Wilcox Associates

P.O. Box 139

Tel:  (816) 443-2494

McFarland, WI 53558

Date of Evaluation:  04/30/94

Tel:  (608) 838-8786

 