Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Programs - LG 113

Issue Date: August 3, 2015

Franklin Fueling Systems

Incon TS-1001/2001, TS-5, TS-550, TS-5000, TS-550 evo, and TS-5000 evo with
FMP-DIS Discriminating Interstitial Sensor and FMP-EIS Electro-Optical Interstitial Sensor

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

conductivity, electro-optic

Test Results:

 

unleaded gasoline

diesel*

waste oil

water

E85

TFMP-DIS

         

Detection time (min)

<1

<1

<1

<1

<1

Fall time (min)

<1

<1

<1

<1

<1

Threshold Level (in)

0.2996

0.3057

0.2934

0.3134

0.2886

TFMP-EIS

         

Detection time (min)

<1

<1

<1

<1

<1

Fall time (min)

<1

<1

<1

<1

<1

Threshold Level (in)

0.2718

0.2728

0.2534

0.2792

0.2700

Manufacturer and evaluator claim that sensors will respond to any liquid. Evaluations determined these sensors' responses to the liquids shown above.
*Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

Comments:

Sensors can be removed, cleaned and reinstalled if an alarm is triggered or if the sensor is periodically tested. The FMP-DIS and FMP-EIS sensors are identical in operation and communication to Franklin Fueling System's TSP-DIS and TSP-EIS sensors. The FMP-DIS and FMP-EIS sensors can connect to any INCON console with no software or setup changes. FMP-DIS and FMP-EIS sensors can be distinguished from TSP-DIS and FMP-EIS sensors by the part number on the label that begins with "FMP" instead of "TSP." The TSP-DIS, TSP-EIS, FMP-DIS and FMP-EIS sensors appear as the same device from the automatic tank gauge.

The FMP-DIS sensor uses two conductive pins to detect whether the liquid is water or fuel. When tested in three mixtures of water/E85 (i.e., 20%/80%; 30%/70%; and 70%/30%), the FMP-DIS sensor went into alarm when subjected to the upper and lower layers of water/E85. For the upper layer containing hydrocarbon, the DIS sensor indicated a product or alarm as designed. For the lower layer of liquid, the DIS sensor indicated a "water" alarm.

 

Franklin Fueling Systems

Evaluator:  Ken Wilcox Associates

3760 Marsh Road

Tel:  (816) 443-2494

Madison, WI 53718

Date of Evaluation:  04/02/15

Tel: (800) 225-9787

 

E-mail: info@franklinfueling.com

 

URL: www.franklinfueling.com

 
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.