Issue
Date: December 22, 2003
Revision Date: May 21, 2007
Veeder-Root
TLS-350 Series, EMC,
EMC-PC, EMC Enhanced, EMC-PC Enhanced, and Red Jacket ProMax
with Magnetostrictive Sump Sensor Series 857060-xxx* and 857080-xxx*
INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector:
|
Output
type:
|
qualitative,
discriminating
|
|
Sampling
frequency:
|
continuous
|
|
Operating
principle:
|
magnetostrictive
probe with dual floats
|
Test Results:
*California
requires annual certification of all leak detection equipment.
The certification of discriminating sensors should include
functional testing of both water and product detection capabilities.
24"
Sump Sensor
Series 857060-xxx* and 857080-xxx*
|
unleaded gasoline |
diesel |
water |
gas
on 7” of water
(fuel alarm in presence of water) |
diesel
on 7” of water
(fuel alarm in presence of water) |
| Detection
time (sec) |
~10 |
~10 |
~10 |
~10 |
~10 |
| Fall
time (sec) |
~10 |
~10 |
~10 |
~10 |
~10 |
|
Minimum
product level (in)
|
1.368
|
1.329
|
1.614
|
1.116
|
1.101
|
xxx* - designates sensors in the 857060 and 857080 series containing:
857060 and 857080-101, -102, -111, -112, -121, -122, -211,
-212, -221, and -222
Comments:
One sensor length (24") was evaluated.
Results are typical for the other sensors in the 857060-xxx
and 857080-xxx series, regardless of length and programmability
options.
All sensors are based on the use of a magnetostrictive sensor
that is equipped with two floats. The lower float will only
float on water. The upper float will float on fuel as well
as water.
Results for the "water alarm" threshold will vary
based upon programmed alarm levels.
The "fuel alarm" is based upon a fixed threshold
and is not programmable.
Systems containing these sensors can be programmed to alarm
continuously and to shut down the dispensing system.
Sensor will issue an alarm if it is raised from the bottom
of the containment vessel.
Sensors are reusable.
Vendor claims sensors are easily removable, cleaned, and reinstalled
if an alarm is triggered or for periodic testing.
|
Veeder-Root
|
Evaluator:
Ken Wilcox Associates
|
|
125
Powder Forest Dr.
|
Tel:
(816) 443-2494
|
|
Simsbury,
CT 06070-2003
|
Dates
of Evaluation: 5/17/04, 4/21/05, 5/27/05, 4/26/07
|
|
Tel:
(860) 651-2700
|
|
|
E-mail:
dhalla@veeder.com
|
|
|
URL:
www.veeder.com/dynamic/index.cfm
|
|
|