Issue
Date: November 22, 1995
Revision Date: April 27, 2005
Purpora
Engineering, Inc. (originally listed as Heath Consultants,
Inc.)
Petro
Tite Line Tester
LINE TIGHTNESS
TEST METHOD
|
Certification
|
Leak
rate of 0.1 gph with PD = 99.99% and PFA = 0.34%.
|
|
Leak
Threshold
|
0.05
gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold.
Vendor claims this equipment can detect leaks at .01 gph,
and trains operators to declare leaks at .01 gph.
|
|
Applicability
|
Gasoline,
diesel, aviation fuel, fuel oil #4.
|
|
Specification
|
System
tests fiberglass and steel pipelines.
Tests are conducted at 150% operating pressure.
Mechanical line leak detector must be removed from pipeline
for duration of test.
|
|
Pipeline
Capacity
|
Maximum
of 129 gallons.
|
|
Waiting
Time
|
None
between delivery and testing.
None between dispensing and testing.
|
|
Test
Period
|
Minimum
of 1 hour pretest for 3 inch diameter fiberglass piping
in accordance with Petro Tite test procedures. Pretest
is not required for steel piping and not required for
fiberglass piping with a diameter less than 3 inches.
Minimum of 30 minute (two 15 minute readings) test when
the detected leak does not exceed 0.005 gph, or minimum
of 1 hour (four 15 minute readings) test when the detected
leak is more than 0.005 gph for the first 30 minutes.Test
data are acquired and recorded manually..
|
|
Calibration
|
System
must be checked annually and, if necessary, calibrated
in accordance with manufacturer's instructions.
|
|
Purpora
Engineering, LLC
|
Evaluator: Ken Wilcox Associates
|
|
P.O.
Box 170591
|
Tel: (816) 443-2494
|
|
Milwaukee,
WI 53207
|
Dates
of Evaluation: 03/11/91, 05/06/01
|
|