Issue Date:  November 7, 2001

 

OMNTEC Mfg., Inc.

Controller Models OEL 8000 11, K-OEL 8000 11 with
Liquid level sensors BX-PDS, BX-PDWF, BX-PDWS

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative, discriminating

Sampling frequency:

continuous

Operating principle:

optical sensor, conductivity

 

Test Results:
*California requires annual certification of all leak detection equipment. The certification of discriminating sensors should include functional testing of both water and product detection capabilities.

 

Model BX-PDS, BX-PDWF, and BX-PDWS: Sensors can only respond to liquid directly in contact with the detection element, and are unable to detect a product release floating on an existing pool of water whose height exceeds the level of the detection element.

 

unleaded gasoline

diesel

water

BX-PDS

Detection time (sec)

< 1

< 1

< 1

Fall time (sec)  

< 1

< 1

< 1

Lower detection limit (cm)

0.464

0.468

0.500

BX-PDWF

 

 

 

Detection time (sec)

< 1

< 1

< 1

Fall time (sec)  

< 1

< 1

< 1

Lower detection limit (cm)

0.63

0.46

0.40

BX-PDWS

 

 

 

Detection time (sec)

< 1

< 1

< 1

Fall time (sec)  

< 1

< 1

< 1

Lower detection limit (cm)

0.464

0.468

0.500

 

Specificity Results:
Manufacturer claims sensors will respond to any liquid after its threshold is exceeded.  
No additional materials tested.

Manufacturer's Specifications:
Manufacturer states that the sensors can also be tested from their location without removal.  
The test procedure is as follows: When the test button on the controller is pressed, the normally closed light beam is opened, which simulates an actual leak occurrence, sending an alarm signal to the controller.  
The controller responds to the alarm signal by turning on an audio/visual alarm and printing the test results.

Comments:
Optic sensor BX-PDS also contains a conductivity sensor to determine if the product is hydrocarbon or water.

 Simulating a leak occurrence from the controller does not meet the 12 month operability certification requirement of section 2638(a) of the California Code of Regulations, title 23.

 

OMNTEC Mfg., Inc.

Evaluator:  Ken Wilcox Associates

1993 Pond Rd.

Tel:  (816) 443-2494

Ronkonkoma, NY  11779

Dates of Evaluation:  11/15/00

Tel:  (631) 981-2001

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.