Issue Date: November 14, 1997
Revision Date: October 18, 2002
 

OPW Fuel Management Systems
(originally listed as Emco Electronics, Tuthill Transfer Systems)

EECO 1500, 2000, 3000, Leak Sensor, Leak Sensor II, Leak Sensor Jr.
with Q0002-001, Q00002-005 Sensors

OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

adsistor (Q0002-001sensor), metal oxide semiconductor (Q0002-005 sensor)

 

Test Results:

unleaded gasoline

synthetic gasoline

JP-4 jet fuel

Q0002-001 Sensor

Accuracy* (%)

100

 

100

Detection time* (min:sec)

19:32

 

09:16

Fall time* (hh:mm:ss)

00:32:30

 

>01:05:33

Lower detection limit (ppm)

1000

 

500

Q0002-005 Sensor

 

 

 

Accuracy* (%)

100

100

100

Detection time* (min:sec)

00:30

00:28

01:01

Fall time* (min:sec)

03:34

02:40

05:33

Lower detection limit (ppm)

100

100

100

*For tests conducted with 1000 ppm of test gas.

** See Glossary

Specificity Results (in addition to above):
Activated:  n-hexane, toluene, xylene(s).

Comments:
Q0002-001 sensor is not for use with synthetic gasoline.

 

OPW Fuel Management Systems

Evaluator:  Carnegie Mellon Research Institute

6900 Santa Fe Dr.

Tel:  (412) 268-3495

Hodgkins, IL 60525

Date of Evaluation:  11/12/96, 10/18/96

Tel: (708) 485-4200

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.