Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Programs - LG 113

Issue Date: November 22, 1995
Revision Date: November 14, 1997
 

PermAlert

PAL-AT Models AT20C, AT50C, AT40K with PHFW Hydrocarbon Probe and Type 1 or Type 2 Sensor

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

Detector:

Output type

qualitative

Sampling frequency

continuous

Operating principle

product soluble

Test Results:

unleaded gasoline

synthetic gasoline

Type 1 Sensor

Detection time (sec)

24

9

Fall time

N/A*

N/A

Lower detection limit (cm)

0.01

0.01

Type 2 Sensor

 

 

Detection time (min:sec)

14:39

08:45

Fall time

N/A

N/A

Lower detection limit (cm)

0.01

0.01

* See glossary.

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s).

Manufacturer's specifications:
Operating temperature range is 0 degrees F to 90 degrees F.

Comments:
The detector is not reusable and must be replaced after contact with hydrocarbons. California regulations require sensors to be tested annually to verify proper operation. This sensor is a self-destruct type and therefore cannot be used in California.

 

PermAlert

Evaluator:  Carnegie Mellon Research Institute

7720 N. Lehigh Ave.

Tel:  (412) 268-3495

Niles, IL 60714-3491

Date of Evaluation:  09/15/92

Tel:  (847) 966-2235

 