Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Program - LG 113

Issue Date: November 22, 1995
Revision Date: June 5, 2002
 

Gems Sensors, Inc.
(originally listed as Warrick Controls, Inc.)

Model 5700 Meter with PVP-2 Sensor

OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)

Detector:

Output type:

quantitative

Sampling frequency:

continuous

Operating principle:

adsistor

 

Test Results:

 

 

unleaded gasoline

synthetic gasoline

JP-4 jet fuel

Accuracy (%)

25.4

-100.0

157.1

Bias (%)

14.4

-100.0

108.3

Precision (%)

7.6

N/D*

20.4

Detection time (min)

>60

N/A*

>60

Fall time (min)

38

N/A

>60

Lower detection limit (ppm)

1353.3

N/D

N/D

* See glossary.

Specificity Results:
Not Activated:  n-hexane, toluene, xylene(s).

 

Gems Sensors, Inc.

Evaluator:  Carnegie Mellon Research Institute

1 Cowles Rd.

Tel:  (412) 268-3495

Plainville, CT 06062-1198

Date of Evaluation:  09/10/91

Tel: (800) 378-1600

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.