Issue Date: April 18, 1997
Updated: January 27, 2011

Franklin Fueling Systems
(Originally listed as INCON Intelligent Controls, Inc.)

Tank Sentinel TS-1000EFI, TS-1001/TS-2001, and TS-5xxx Series with TSP-DIS BriteSensor; Tank Sentinel TS-1000/TS-2000, TS-1001/TS-2001, and TS-5xxx Series with TSP-EIS Standard Sensor; Tank Sentinel TS-1000/TS-2000 with TSP-PS Liquid Contact Sensor

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type: qualitative
Sampling frequency: continuous
Operating principle: opto-electric

Test Results:

TSP-DIS BriteSensor
unleaded gasoline
synthetic
gasoline
diesel
fuel **
heating
oil #2
water
E 85
Detection time (min:sec)
03:13
03:17
3:00
3:02
03:18
--
Fall time (min)
<1
<1
<1
<1
<1
--
Product activation height (cm)
1.60
N/D*
N/D
N/D
1.92
--
Lower Detection Limit (cm)
1.60
1.60
1.50
1.50
1.62
--
TSP-EIS Standard Sensor
 
Detection time (min:sec)
03:01
03:17
3:00
3:02
03:07
<1
Fall time (min)
<1
<1
<1
<1
<1
<1
Product activation height (cm)
1.50
N/D
N/D
N/D
N/D
1.99
Lower Detection Limit (cm)
1.50
1.60
1.50
1.50
1.50
1.99
TSP-PS Liquid Contact Sensor
 
Detection time (min:sec)
01:14
01:13
01:10
01:16
01:25
--
Fall time (min)
<1
<1
<1
<1
<1
--
Product activation height (cm)
1.37
N/D
N/D
N/D
N/D
--
Lower Detection Limit (cm)
1.22
1.21
1.20
1.24
1.32
--

* See glossary.

**This evaluation determined the sensor's responses to the liquids shown above.  Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded.  Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

Comments:

Comparison of Tank Sentinel TS-1001/TS-2001 and TS-5xxx series consoles with Tank Sentinel TS-1000 (including EFI) /TS-2000 series consoles showed comparable results when evaluated with representative sensors. Sensors are reusable.

Franklin Fueling Systems Evaluator: Carnegie Mellon Research Institute
3760 Marsh Road Tel: (412) 268-3495
Madison, WI 53718 Dates of Evaluation:  12/09/94, 01/30/96,
Tel: (800) 225-9787 07/02/93
email: info@franklinfueling.com Evaluator: Ken Wilcox Associates
URL: www.franklinfueling.com Tel: (816) 443-2494
Date of Evaluation: 4/01/2008

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded "Disclaimer" page.

 

 
 

.