Issue Date:  November 7, 2001
Revision Date: August 18, 2005

OPW Fuel Management Systems
(originally listed as Petro Vend, Inc.)

SiteSentinel Controller with
Optical Sensor Part #30-3223

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

Optical (Part #30-3223) 

Test Results:

Unleaded gasoline

diesel

water

Part #30-3223

 

 

 

Detection time (sec)

<1

<1

<1

Fall time (sec)

<1

<1

<1

Lower detection limit (in)

0.571

0.561

0.592

Specificity Results:
Part #3223 works with any liquid.

OPW Fuel Management Systems

Evaluator:  Ken Wilcox Associates

6900 Santa Fe Dr.

Tel:  (816) 443-2494

Hodgkins, IL 60525-9909

Dates of Evaluation:  08/03/00

Tel:  (708) 485-4200

 