PermAlert

PAL-AT Models AT20C, AT50C, AT40K with PHL Hydrocarbon Sensor

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

electrical conductivity

 

Test Results:

 

 

unleaded gasoline

Response time (min)

1.13

Recovery time (min)

8.83

Product activation height (cm)

0.53

Lower detection limit (cm)

0.38

Specificity Results (in addition to above):
Activated:  synthetic gasoline, diesel, heating oil #2.
Not activated: water.

Comments:
Sensors are reusable.

 

PermAlert

Evaluator:  Carnegie Mellon Research Institute

7720 N. Lehigh Ave.

Tel:  (412) 268-3495

Niles, IL 60714-3491

Date of Evaluation:  02/05/92

Tel:  (847) 966-2235

 