Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Programs - LG 113

Issue Date: November 22, 1995
Revision Date: January 11, 2001
 

Pneumercator Company, Inc.

LDE 700, LDE 740, LDE 9000 with Sensor Probe Models 9-901, 9-902, 9-903

INTERSTITIAL DETECTOR (LIQUID-PHASE)

 

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

capacitance

Test Results:

 

unleaded gasoline

synthetic gasoline

Detection time (sec)

<1

<1

Fall time

manual reset

manual reset

Lower detection limit (cm)

 

 

    9-901

0.32

0.36

    9-902

0.36

0.34

    9-903

0.76

0.74

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.

Comments:
Sensors are reusable.
Capacitance probes do not work with oxygenated fuels.

 

Pneumercator Company, Inc.

Evaluator:  Ken Wilcox Associates

120 Finn Court

Tel:  (816) 443-2494

Farmingdale, NY 11735

Date of Evaluation:  12/14/93

Tel:  (631) 293-8450

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.