Issue Date: November 22, 1995
        Revision Date: December 6, 2002
Agar Corp.
LEAKWISE Groundwater Monitor
        ID-220 Series Hydrocarbon on Water Detector System
      Out-of-Tank Product Detector (Liquid-Phase)
Detector
| Output Type | Qualitative | 
|---|---|
| Sampling Frequency | Continuous | 
| Operating Principle | Radio frequency (RF) attenuation | 
Test Results
| Unleaded Gasoline | Synthetic Gasoline | |
|---|---|---|
| Detection time (sec) | <1 | <1 | 
| Fall time (sec) | <1 | <1 | 
| Lower detection limits (cm) | ||
| "Standard" setting | 0.16 | 0.32 | 
| "Sensitive" setting | 0.03 | 0.03 | 
Specificity Results
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.
Manufacturer's specifications
Operating range:
| Resolution | 0.5 mm of hydrocarbon on water or brine | 
|---|---|
| Variation | Groundwater fluctuation of +/- 1 meter standard (larger variations optional) | 
| Oil thickness | 0.3 - 25 mm optional (higher ranges available) | 
| Temperature | 0 - 70 degrees C (higher available) | 
Comments
Sensors are reusable.
Color coded signal lights indicate the presence of air, water, and hydrocarbon liquid when activated (yellow, green, and red, respectively).
- Agar Corp.
 5150 Tacoma Drive
 Houston, TX 77041
 Tel: (832) 476-5100
- Evaluator: Ken Wilcox Associates
 Tel: (816) 443-2494
 Date of Evaluation: 11/15/91
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.