Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Program - LG 113

Issue Date: August 23, 1999
Revision Date: March 10, 2000

 

Caldwell Systems Corp.

Tank Manager Liquid Sensor, Version TMLIQ

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:           

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

ultrasonic

Test Results:

Horizontal Position

unleaded gasoline

diesel

water

Response time (sec)

<1

<1

<1

Recovery time (sec)

<1

<1

<1

Lower detection limit (cm)

1.28

1.30

2.43

Precision - standard deviation (cm)

0.05

0.06

0.25

Vertical Position

 

 

 

Response time (sec)

<1

<1

<1

Recovery time (sec)

<1

<1

<1

Lower detection limit (cm)

8.56

7.59

9.27

Precision - standard deviation (cm)

0.22

0.11

0.44

Specificity Results:
Evaluator claims sensor will detect fuels or other liquids.

Comments:
Sensor is designed to alarm only when liquid is present from one end of sensor to the other.  Therefore, sensor orientation (vertical or horizontal) will effect lower detection limit.
Sensors are reusable.

 

Caldwell Systems Corp.

Evaluator:  Ken Wilcox Associates

600 South Sunset Street, Unit D

Tel:  (816) 443-2494

Longmont, CO 80501

 

Tel:  (303) 684-8436

Date of Evaluation:  11/09/98

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.