Issue Date: November 22, 1995
Revision Date: September 2, 2008
 

Estabrook EZY CHEK Systems 
(originally listed as Horner EZY CHEK)

EZY-Chek Manual Line Leak Detector (for Rigid Pipelines)

LINE TIGHTNESS TEST METHOD

Certification Leak rate of 0.1 gph with PD = 98.0% and PFA = 1%.
Leak Threshold 0.05 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel, fuel oil #4. 
Other liquids may be tested after consultation with the manufacturer.
Specification System tests fiberglass and steel pipelines. 
Tests are conducted at 150% operating pressure. 
Mechanical line leak detector must be removed from pipeline for duration of test.
Pipeline Capacity Maximum of 129 gallons.
Waiting Time None between delivery and testing. None between dispensing and testing.
Test Period Minimum of 1 hour, 30 minutes. 
Data are collected every 15 minutes. 
Testing period consists of a monitor mode and test mode. 
Data are collected in the monitor mode until two consecutive records are within 0.01 gallon of each other.
Four data points must be taken in test mode for a final gph result. 
Test data are acquired and recorded manually. 
Manual calculations performed by the operator on site.
Calibration

No temperature sensors used. 
No calibration required. 
System must be checked annually in accordance with manufacturer's instructions.
Technicians must be certified by the manufacturer prior to using this equipment and recertified every two years.

Estabrook EZY CHEK Systems
1505 Woodside Ave.
Essexville, MI  48732
Tel:  (989) 891-9868
E-mail:  sales@ezychek.com
URL:  www.ezychek.com
Evaluator:  Ken Wilcox Associates
Tel:  (816) 443-2494
Date of Evaluation:  07/09/92, 05/31/08