Issue Date: October 13, 2006
Revision Date: September 2, 2008
Estabrook
EZY CHEK Systems
(originally listed as
Horner EZY CHEK)
EZY-Chek
Manual Line Leak Detector (for Flexible Pipelines)
LINE TIGHTNESS
TEST METHOD
Certification |
Leak
rate of 0.1 gph with PD = 99.8% and PFA = 0.2%. |
Leak
Threshold |
0.05
gph.
A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this
threshold. |
Applicability |
Gasoline,
diesel, aviation fuel, fuel oil #4.
Other liquids may be tested after consultation with the
manufacturer. |
Specification |
System
tests flexible pipelines.
Tests are conducted at 150% operating pressure.
Mechanical line leak detector must be removed from pipeline
for duration of test. |
Pipeline
Capacity |
Maximum
of 101 gallons (example: 275 feet of 3 inch line). |
Waiting
Time |
None
between delivery and testing. None between dispensing
and testing. |
Test
Period |
Under
ideal conditions 30 minutes; actual test time will depend
on line size and temperature conditions at the site.
Data are collected every 15 minutes.
Three consecutive consistent readings are required for a valid test.
Data from the evaluation suggests that the actual minimum test time for a line this size is 2 hours.
Consistent readings for three consecutive readings are
required for a valid test. Data from the evaluation suggests
that the actual minimum test time for a line this size
is 2 hours.
Test data are acquired and recorded manually.
Manual calculations performed by the operator on site. |
Calibration |
No
temperature sensors used.
No calibration required.
System must be checked annually in accordance with manufacturer's
instructions.
Technicians must be certified by the manufacturer prior to using this equipment, and recertified every two years. |
Estabrook