Issue Date: April 25, 2012

Fairbanks Environmental Ltd.

Wetstock Wizard Version 4.4

STATISTICAL INVENTORY RECONCILIATION TEST METHOD (QUALITATIVE)

Certification Leak rate of 0.2 gph with PD > 99% and PFA < 1% for both single and manifolded tank systems.
Leak Threshold 0.10 gph. 
If the absolute value of the calculated leak rate (gain or loss) is less than the leak threshold and the minimum detectable leak rate is less than or equal to 0.2 gph, the test result is "pass." If the absolute value of the calculated leak rate is greater than or equal to the leak threshold, the result is "fail." If the minimum detectable leak rate exceeds 0.2 gph and the absolute value of the calculated leak rate is less than the leak threshold, the test result is "inconclusive."
Applicability Gasoline, diesel, kerosene. 
Tank Capacity Maximum of 45,000 gallons for single tanks. 
Maximum of 45,000 gallons cumulative capacity for manifolded tank systems with no more than 4 tanks in system.
Data Requirement Minimum of 30 days of product level and throughput data.
Comments Inventory data was submitted by vendor to evaluator who adjusted data and returned to vendor for analysis.
49% of data sets were from manifolded tank systems. 
Of 41 data sets submitted for evaluation, 36 were analyzed with conclusive results. 
Median monthly throughput of tanks evaluated was 25,173 gallons. 
Leak rates of 0.05, 0.1, and 0.2 gph were used in evaluation.
Results of evaluation is applicable only for tanks using ATGs to collect data.

 

Faribanks Environmental, Ltd.

Evaluator:  Ken Wilcox Associates

The Technology Management Center

Tel:  (816) 443-2494

Moss View Lane

Date of Evaluation:  11/10/2004 (rev. 8/10/2006)

Skelmersdale, Lancashire, UK

 

Phone +44 (0) 1695 51775  

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.