Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Program - LG 113

Issue Date: November 22, 1995
Revision Date: March 10, 2000
 

FCI Environmental, Inc.

Analog Hydrocarbon Probe AHP-100, Digital Hydrocarbon Probe DHP-100

OUT-OF-TANK PRODUCT DETECTOR (VAPOR-PHASE)

Detector:

Output type:

quantitative

Sampling frequency:

continuous

Operating principle:

fiber optic

 

Test Results (for tests conducted with 1000 ppm test gas):

 

 

AHP-100

unleaded gasoline

synthetic gasoline

 

xylene

 

benzene

 

2-methylbutane

Relative accuracy* (%)

12

22

2

35

N/R*

Bias (%)

-7

-2

1

-23

N/R

Precision (%)

4

15

1

11

N/R

Detection time (min)

<1

<1

<1

<1

N/R

Fall time (min)

<1

<1

<1

<1

N/R

Lower Detection Limit (ppm)

137

220

84

519

N/R

DHP-100

 

 

 

 

 

Relative accuracy* (%)

18

29

0

17

N/R

Bias (%)

1

-12

0

-9

N/R

Precision (%)

9

10

0

11

N/R

Detection time (min)

<1

<1

<1

<1

N/R

Fall time (min)

<1

<1

<1

<1

N/R

Lower Detection Limit (ppm)

73

118

45

280

N/R

* See glossary.

Test Results (for tests conducted with 10 ppm test gas):

 

AHP-100

unleaded gasoline

synthetic gasoline

 

diesel

JP-4

jet fuel

JP-8

jet fuel

 

p-xylene

kero-sene

Lower Detection Limit (ppm)

 

9.25

 

13.26

 

5.79

 

5.26

 

10.89

 

12.94

 

14.65

Specificity Results (%) (corrected for sensitivity differences):

 

AHP-100

DHP-100

 

AHP-100

DHP-100

unleaded gasoline

93

101

xylene

103

N/R

synthetic gasoline**

100

92

toluene

96

97

synthetic gasoline***

98

88

pentane

N/R

N/R

JP-4 jet fuel

105

109

methane

N/R

N/R

benzene

76

89

butane

N/R

N/R

trimethylbenzene

107

104

2-methylbutane

N/R

N/R

p-xylene

101

100

n-hexane

N/R

108

** EPA March 1990 protocol
*** Radian June 1990 protocol

Comments:
1000 ppm tests used a certified blend of concentrated gas to simulate a leak.  10 ppm test used a measured quantity of liquid product to simulate a leak.

 

FCI Environmental, Inc.

Evaluator:  Ken Wilcox Associates

1181 Grier Dr., Bldg. B

Tel:  (816) 443-2494

Las Vegas, NV 89119

Dates of Evaluation:  03/07/94, 12/05/94

Tel:  (800) 510-3627

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.