Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Program - LG 113

Issue Date: July 27, 2006
Revision Date: February 13, 2015

Franklin Fueling Systems

INCON T1 Series, TS-750, TS-1000, TS-1001, TS-2000, TS-2001, INCON T5 Series, TS-5, TS-608, TS-550, TS-550 evo, TS-5000, TS-5000 evo, Colibri CL6 & TS-CL6 Series SCALD 2.0
(INCON TSP-LL2 and FMP-LL3 Magnetostrictive Probe)

CONTINUOUS IN-TANK LEAK DETECTION METHOD (CONTINUOUS AUTOMATIC TANK GAUGING)

Certification Leak rate of 0.2 gph with PD > 99% and PFA < 1%.
Leak Threshold 0.10 gph for single and manifolded tank systems.
A tank system should not be declared tight and a message printed for the operator, if the test results indicate a loss or gain that exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel, fuel oil #4, biodiesel blands B6-B20 meeting ASTM D7467, biodiesel B100 meetign ASTM D6751. Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility - see "Disclaimer".
Tank Capacity Maximum of 49,336 gallons for single tanks and for all tanks manifolded together.
Tank must be between 14 and 93.5% full.
Throughput Monthly maximum of 257,818 gallons.
Waiting Time None between delivery and data collection when difference between product in tank and product delivered is 6.0 degrees F or less.
Test Period Data collection time ranges from 5 to 28 days. Data sampling frequency is > 1 per second.System collects data at naturally occurring product levels without interfering with normal tank operation, and discards data from unstable periods when system performs test.
Temperature Average for product is determined by a minimum of 5 thermistors.
Water Sensor Must be used to detect water ingress.
Minimum detectable water level in the tank is 0.208 inch (0.44 inch using model TSP-IGF4P).
Minimum detectable change in water level is 0.011 inch (0.013 inch using model TSP-IGF4P).
Calibration Thermistors and probe must be checked and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments System reports a result of “pass” or “fail”.
Evaluated using both single and manifolded tank systems with probes in each tank.
Tests only the portion of the tank containing product.
As product level is lowered, the leak rate in a leaking tank decreases (due to lower head pressure).
Consistent testing at low levels could allow a leak to remain undetected. EPA leak detection regulations require testing of the portion of the tank system which routinely contains product.
TS 750, 1000 and 1001 can support up to 4 tanks.
TS 2000 and 2001 can support up to 8 tanks.
TS 5 can support up to 12 tanks. TS 608 can support up to 8 tanks.
TS 550, TS-550 evo and 5000 can support up to 48 tanks.
Colibri CL6 and TS-CL6 can support up to 6 tanks.
TS 750 and 2000 do not provide fuel logistics, remote monitoring and other business management options available with TS 1000, 1001, and 2001.
The database for evaluation of the system includes sites with vapor recovery and blending dispensers.

Franklin Fueling Systems Evaluator:  Ken Wilcox Associates
3760 Marsh Road Tel:  (816) 443-2494
Madison, WI 53718 Date of Evaluation:  07/11/2003, 03/18/06, 08/18/09, 07/06/11, 04/09/12, 08/04/14
Tel: (800) 225-9787
E-mail: info@franklinfueling.com  
URL: www.franklinfueling.com

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.