Issue Date: August 15, 2022
Franklin Fueling Systems
Franklin Fueling Systems EVO 200, EVO 400, EVO600, and EVO6000 with FMP-DIS-U Discriminating Interstitial Sensor and FMP-EIS-U Electro-Optical Interstitial Sensor
Interstitial Detector (Liquid-Phase)
Detector
| Output Type | Qualitative | 
|---|---|
| Sampling Frequency | Continuous | 
| Operating Principle | Float switch | 
Test Results
| Unleaded Gasoline | Diesel* | Waste oil | Water | E85 | |
|---|---|---|---|---|---|
| FMP-DIS-U | |||||
| Detection time (min) | <1 | <1 | <1 | <1 | <1 | 
| Fall time (min) | <1 | <1 | <1 | <1 | <1 | 
| Threshold level (in) | 0.4293 | 0.4397 | 0.4208 | 0.4594 | 0.4240 | 
| FMP-EIS-U | |||||
| Detection time (min) | <1 | <1 | <1 | <1 | <1 | 
| Fall time (min) | <1 | <1 | <1 | <1 | <1 | 
| Threshold level (in) | 0.4478 | 0.4430 | 0.4317 | 0.4566 | 0.4507 | 
Applicability
California Code of Regulations require a written statement of compatibility for systems containing products other than those used in this evaluation.
Comments
Sensors can be removed, cleaned and reinstalled if an alarm is triggered or if the sensor is periodically tested.
- Franklin Fueling Systems
 3760 Marsh Road
 Madison, WI 53718
 Tel: (800) 225-9787
 E-Mail: info@franklinfueling.com
 URL: www.franklinfueling.com
- Evaluator:  Ken Wilcox Associates
 Tel: (816) 443-2494
 Date of Evaluation: 05/02/2017, 11/8/2018
 
 
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.