Issue Date: August 07, 2017

Franklin Fueling Systems

Incon TS-1001/2001, TS-5, TS-550, TS-5000, TS-550 evo, TS-5000 evo, EVO400, EVO200, and S940 Alarm Console with FMP-ULS Universal Liquid Sensor, FMP-UHS Universal Hydrostatic Sensor, FMP-ULS-C Universal Liquid Sensor Chemical, FMP-ULS-PS Universal Liquid Sensor Position Sensitive sensors

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type: qualitative
Sampling frequency: continuous
Operating principle: float/reed switch

Test Results:

 
Unleaded gasoline
Diesel
Biodiesel*
Water
E85
Brine
FMP-ULS            
Detection time (min)
<1
<1
<1
<1
<1
Fall time (min)
<1
<1
<1
<1
<1
Threshold Level (in)
1.0155
0.9944
0.9925
0.8775
1.0198
FMP-UHS
 
Detection time (min)
<1
<1
<1 
<1
<1
<1
Fall time (min)
<1
<1
 <1
<1
<1
<1
Threshold Level (in)
0.9602
0.9144
0.9218 
0.0032
0.9397
0.7561
FMP-ULS-PS
 
Detection time (min)
<1
<1
 <1
<1
<1
Fall time (min)
<1
<1
 <1
<1
<1
Threshold Level (in)
1.4915
1.4882
1.4758
1.3770
1.4962
 
 
FMP-ULS-C
Lubrizol**
Afton**
Detection time (min)
<1
<1
Fall time (min)
<1
<1
Threshold Level (in)
1.1707
1.1281
FMP-ULS-PS
Detection time (min)
<1
<1
Fall time (min)
<1
<1
Threshold Level (in)
1.4959
1.4290


*Evaluations determined these sensors' responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses. 
** Manufacturer and evaluator claim that responses to Lubrizol 9888 and 9888C would be expected to be very similar to each other. Responses to Afton OTR 8332G. and OTR 8843G would be expected to be very similar to each other.

Comments:
Sensor TSP-UHS is the same as the TSP-ULS sensor except that the float has been inverted so that it may be used to monitor the brine reservoir of containment sumps. An alarm condition will occur when the fluid level drops below the end of the sensor. The FMP-ULS-PS is a position sensitive float switch that issues an alarm if not installed properly at the bottom of the intestinal or sump. 
Sensors are reusable.

Franklin Fueling Systems Evaluator: Ken Wilcox Associates
3760 Marsh Road Tel: (816) 443-2494
Madison, WI 53718 Date of Evaluation: 05/02/2017
Tel: (800) 225-9787  
email: info@franklinfueling.com  
URL: www.franklinfueling.com  

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded "Disclaimer" page.

 

 
 

.