Issue
Date: March 1, 2002 Pneumercator Company, Inc. LC 2000, TMS 2000, TMS 3000 with INTERSTITIAL
DETECTOR (LIQUID-PHASE)
Detector:
Test Results: Model ES825-200(F): This sensor can only respond to liquid directly in contact with the detection element, and is unable to detect a product release floating on an existing pool of water whose height exceeds the level of the detection element.
Specificity Results: Manufacturer claims sensors will respond to any liquid after sensor's threshold is exceeded. Manufacturer's Specifications: All the sensors are designed to connect to a controller system that indicates the status of the sensor. Manufacturer indicates that discriminating sensors ES 825-200F and 200XF incorporate an optical liquid sensor and a conductivity sensor. These sensors discriminate between product and water by determining if the optical sensor, which responds to any liquid, or the conductivity sensor, which responds only to water, causes an alarm. Comments: "F", "XF", and "CF" are variations of the same sensor distinguished by the material they are made of, such as PVC and Teflon.
|
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Appearance
on this list is not to be construed as an endorsement by any regulatory
agency nor is it any guarantee of the performance of the method or equipment. |