Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Programs - LG 113

Issue Date: March 11, 2011

Preferred Utilities Manufacturing Corporation
TG-EL-D4A Fuel Sentry Control Unit,
PS-LDS Non-Discriminating Pump Set Leak Detector Switch
OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

Detector Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Reed Switch/Float
Test Results PS-LDS Pump Set Leak Detector Switch (Sumps and Containments)
Unleaded Gasoline
Diesel*
Water
Detection time (sec)
Did not float
<5
<5
Fall time (sec)
Did not float
<5
<1
Lower detection limit (in)
Did not float
1.322
1.187
Comments Control panel: Six intrinsically safe sensor inputs can be used for level indication and/or leak detection. Provides audible and visual alarms.
Sensor: Primarily designed for use with diesel fuel and other distillates but can be used with other fluids - see manufacturer for specific limitations.
*This evaluation determined the sensors' responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Detects leakage into the base pan of a pump set.
All stainless steel.

 

Preferred Utilitites Manufacturing Corporation

Evaluator:  Ken Wilcox Associates

31-35 South Street

Tel:  (816) 443-2494

Danbury, CT 06810

Date of Evaluation:  6/17/10

Tel:  (203) 743-6741

 

Email: DCosgrove@preferred-mfg.com  
Website: www.preferred-mfg.com  
  

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.