Issue Date: November 22, 1995
        Revision Date: August 23, 1999
Tidel Engineering, Inc.
EMS-3500 with Monitoring Well Probe Part 301-0641, Sheen Probes Part 301-0687, Tidel Detector #301-0762
Out-Of-Tank Product Detector (Liquid-Phase)
Detector
| Output Type | Qualitative | 
|---|---|
| Sampling Frequency | Continuous | 
| Operating Principle | Conductivity via resistor ladder network (Monitoring Well Probe Part 301-0641), electrical conductivity/hydrocarbon sensitive polymer (Sheen Probes Part 301-0687 and Tidel Detector #301-0762). | 
Test Results
Monitoring Well Probe Part 301-0641
| Unleaded Gasoline | Water | |
|---|---|---|
| Detection time (min:sec) | 0:04 | 0:07 | 
| Fall time (min) | <1 | <1 | 
| Lower detection limit (cm) | 0.32 | 0.32 | 
Sheen Probes Part 301-0687
| Unleaded Gasoline | Water | |
|---|---|---|
| Detection time (min:sec) | 7:45 | 3:35 | 
| Fall time (min:sec) | 18:01 | 16:57 | 
| Lower detection limit (cm) | 0.02 | 0.04 | 
Tidel Detector #301-0762
| Unleaded Gasoline | Water | |
|---|---|---|
| Detection time (min:sec) | 9:31 | 7:05 | 
| Fall time (min:sec) | 55:42 | 17:04 | 
| Lower detection limit (cm) | 0.04 | 0.08 | 
Specificity Results (in addition to above)
Activated: n-hexane, diesel, jet-A fuel, JP-4 jet fuel (except Sheen Probes Part 301-0687), toluene, xylene(s).
Comments
Sensors are reusable.
- Tidel Engineering, Inc.
 2310 McDaniel Dr.
 Carrollton, TX 75006
 Tel: (800) 678-7577
- Evaluator: Carnegie Mellon Research Institute
 Tel: (412) 268-3495
 Date of Evaluation: 02/02/93, 01/31/93 , 03/18/93
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.