Issue Date: November 22, 1995
        Revision Date: August 23, 1999
Tidel Engineering, Inc.
Tidel Detector #301-0324-001, #301-0325-001, #301-0326-001, #301-0326-002
Out-Of-Tank Product Detector (Liquid-Phase)
Detector
| Output Type | Qualitative | 
|---|---|
| Sampling Frequency | Continuous | 
| Operating Principle | Electrical conductivity | 
Test Results
Tidel Detector #301-0324-001, #301-0325-001
| Unleaded Gasoline | Water | JP-4 jet fuel | |
|---|---|---|---|
| Detection time (sec) | 2 | 2 | 1 | 
| Fall time (sec) | 1 | 2 | 2 | 
| Lower detection limit (cm) | 0.16-0.32 | 0.16-0.32 | 0.16-0.32 | 
Tidel Detector #301-0326-001, #301-0326-002
| Unleaded Gasoline | Water | JP-4 jet fuel | |
|---|---|---|---|
| Detection time (sec) | 4 | 7 | 2 | 
| Fall time (sec) | 3 | 4 | 4 | 
| Lower detection limit (cm) | 0.08-0.32 | 0.08-0.32 | 0.08-0.32 | 
Specificity Results (in addition to above)
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s).
Manufacturer's specifications:
Tidel Detector #301-0324-001
| Application: | Liquid sensor, water, used in 4" monitoring well. | 
|---|---|
| Sensor: | Magnetism and conductivity pins. | 
| Detection Range: | 1/8" floating product on groundwater or 1.5" free product. | 
Tidel Detector #301-0325-001
| Application: | Liquid sensor, water or hydrocarbon used in reservoir, sump or pipeline trench. | 
|---|---|
| Sensor: | Magnetism and conductivity pins. | 
| Detection Range: | 1/8" floating product on groundwater or 1.5" free product. | 
Tidel Detector #301-0326-001
| Application: | Liquid sensor, water, used in 2" monitoring well. | 
|---|---|
| Sensor: | Magnetism and conductivity pins. | 
| Detection Range: | 1/8" floating product on groundwater or 2.5" free product. | 
Tidel Detector #301-0326-002
| Application: | Liquid sensor, water, used in annulus of double wall steel tanks. | 
|---|---|
| Sensor: | Magnetism and conductivity pins. | 
| Detection Range: | 1/8" floating product on groundwater or 2.5" free product. | 
Comments
Sensors are reusable.
        Lower detection limit has been statistically determined to be within the range specified above.
- Tidel Engineering, Inc.
 2310 McDaniel Dr.
 Carrollton, TX 75006
 Tel: (800) 678-7577
- Evaluator: Radian Corp.
 Tel: (512) 454-4797
 Date of Evaluation: 07/08/91
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.