Veeder-Root
TLS-300, 300i, TLS-350 Series, TLS-450 Series, TLS-4 8601 Series, Red Jacket ProMax and ProPlus with Discriminating Dispenser Pan Sensor 794380-322, Discriminating Containment Sump Sensor 794380-352
Interstitial Detector (Liquid-Phase)
Detector
| Output Type | Qualitative | 
|---|---|
| Sampling Frequency | Continuous | 
| Operating Principle | Product permeable, reed switch/float | 
Test Results
California requires annual certification of all leak detection equipment. The certification of discriminating sensors should include functional testing of both water and product detection capabilities.
Model 794380-322 and 794380-352: Currently the SWRCB UST Program staff discourages the use of polymer strip discriminating sensors at new installations in California. This is due to concerns about the impact that repeated/prolonged exposure to hydrocarbons may have on the sensor's ability to alarm and recover from alarm reliably. Since current evaluation protocols do not address this issue, no new polymer strip sensors should be installed until new evaluation protocols are in place.
TLS-300, 300i, TLS-350 Series, TLS-450 Series, Red Jacket ProMax and ProPlus
Discriminating Dispenser Pan Sensor 794380-322
| Polymer Strip | Float Switch | |||
|---|---|---|---|---|
| Unleaded Gasoline | Diesel* | Water | ||
| High** | Low** | |||
| Response time (sec) | ~10 min | 2-12 hrs | <1 | <1 | 
| Recovery time (sec) | N/A*** | N/A | <1 | <1 | 
| Lower detection limit - height (in) | N/D*** | N/D | 7.66 | 1.37 | 
| Lower detection limit - thickness (in) | 0.005 | 0.005 | N/A | N/A | 
Discriminating Containment Sump Sensor 794380-352
| Polymer Strip | Float Switch | |||
|---|---|---|---|---|
| Unleaded Gasoline | Diesel* | Water | ||
| High** | Low** | |||
| Response time (sec) | ~10 min | 2-12 hrs | <1 | <1 | 
| Recovery time (sec) | N/A | N/A | <1 | <1 | 
| Lower detection limit - height (in) | N/D | N/D | 12.28 | 1.35 | 
| Lower detection limit - thickness (in) | 0.005 | 0.005 | N/A | N/A | 
TLS-4 8601 Series
(The TLS-4 8601 Series consists of the following derivatives: TLS-4, TLS-4B, TLS-4c, TLS-4i, and TLS-S1 consoles.)
Discriminating Dispenser Pan Sensor 794380-3222
| Unleaded Gasoline | Diesel*** | High***** | Low***** | |
|---|---|---|---|---|
| Detection time (min) | 8.3 | 99.3 | <1 | <1 | 
| Fall time (min) | 10.3 | >24 hrs. | <1 | <1 | 
| Threshold Level (inches) | <0.125 | <0.125 | 7.65 | 1.34 | 
Discriminating Containment Sump Sensor 794380-352
| Unleaded Gasoline | Diesel*** | High***** | Low***** | |
|---|---|---|---|---|
| Detection time (min) | 8.3 | 99.3 | <1 | <1 | 
| Fall time (min) | 10.3 | >24 hrs. | <1 | <1 | 
| Threshold Level (inches) | <0.125 | <0.125 | 12.25 | 1.36 | 
*Evaluations determined these sensors' responses to the liquids shown above and those indicated in the following section. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
**The "high" and "low" refer to high and low level alarm points of float switch sensors.
***See Glossary.
Specificity Results (in addition to above)
Activated:  synthetic gasoline,  jet-A fuel, n-hexane, toluene, xylene(s)
        Not activated:  water (polymer strip only)
Comments
Polymer strip must be air dried after exposure to unleaded fuel.
        Polymer strips must be cleaned with solvent and dried after exposure to diesel.
        Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.
- Veeder-Root
 125 Powder Forest Dr.
 Simsbury, CT 06070-2003
 Tel: (860) 651-2700
 URL: www.veeder.com/us/
- Evaluator: Ken Wilcox Associates
 Tel: (816) 443-2494
 Date of Evaluation: 01/02/95, 06/23/97, 04/20/98, 03/03/08, 12/16/16
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.